- Provides 1700watt(s), 2200VA, 120V power / Surge Suppression is Standard
- Connector(s): Power NEMA 5-15 (F), Power NEMA 5-15 (M) / 6 Outlets
- 11 minute(s) Battery Runtime at Full Load / Attributes include Line interactive
The SmartPro SMART2200NET UPS from Tripp Lite is a line interactive battery backup system that has an output power rating of 2200VA (1700W) to provide plenty of time to save open files and safely power down your system in the event of a blackout. The unit also provides line conditioning, keeping the current to your system even, not allowing spikes or sags to affect your computer. Three built in DB-9 serial ports work with the included PowerAlert software and cabling to provide unattended shutdown or up to three networks running different operating systems in the event of a power failure. Diagnostic LEDs alert you to power problems before they affect equipment. $250,000 Ultimate Lifetime Insurance covers connected equipment against surge damage, including direct lightning strikes.
|
Connectivity
|
|
|
Communication Interface
|
Serial (RS-232)
|
|
Communication Interface
|
Contact closure
|
|
# Ports
|
6
|
|
Connector
|
Power NEMA 5-15 (F)
|
|
Connector
|
Power NEMA 5-15 (M)
|
|
General
|
|
|
Form Factor
|
Tower
|
|
Attributes
|
Line interactive
|
|
Color
|
Gray
|
|
Power
|
|
|
Battery Run Time (max)
|
11 minute(s)
|
|
Power Provided
|
1700 watt(s)
|
|
Power Provided
|
2200 VA
|
|
Power Provided
|
120 V
|
|
Surge Suppression
|
Standard
|
|
Actual Weight
|
80.00 lb(s)
|
|
Compatibility Notes
|
LEDS, ALARMS and SWITCHES
Front panel LEDs: (5) front panel LEDs to indicate BATTERY CHARGE LEVEL, AC LINE POWER STATUS, VOLTAGE REGULATION STATUS, UPS LOAD LEVEL and BATTERY LOW / REPLACE information Alarms: audible alarm with 15 second delay sounds to indicate loss of utility power. Alarm can be silenced by pressing front panel alarm cancel button. Once silenced, alarm will re-sound when approximately 2 minutes runtime remain. Switches: (2) front panel switches -- one on/standby power switch and one dual function "alarm cancel" / "self test" button, plus 1 rear panel system enable switch
SURGE / NOISE SUPPRESSION
AC surge suppression: 480 Joules AC suppression response time: instantaneous EMI / RFI AC noise suppression: Yes
|
|
Contents
|
UPS, PowerAlert Software on CD, (3) network cables 6ft., documentation
|
|
O/S Notes
|
PowerAlert Software Supported Operating Systems
Windows: 98, 98 SE, ME, 2000, 2003, Server 2003 64-bit, XP, XP 64-bit, Vista SUSE Professional 9.3, SUSE Enterprise 9.3 64-bit, SUSE Enterprise 9.3 Solaris 9 (SPARC), Solaris 8 (SPARC), Solaris 10 (SPARC), Solaris 10 (Intel) SCO 6.0 Linux AIX 5.2/5.3
|
|
Physical Dimensions
|
17"h x 9"w x 12.5"d
|
|
Ports/Connectors
|
(6) NEMA 5-15R outlets (1) NEMA 5-15P input power cord, 8ft. 12AWG (1) DB-9 RS-232 serial port (2) DB-9 contact closure ports
|
|
Power Notes
|
OUTPUT
Output capacity: 1700W/2200VA Output nominal voltage: 120VAC Output voltage regulation, line mode: sine wave line voltage 120V (-13% / +5%) Output voltage regulation, battery mode: PWM sine wave output 120V +/-5% Output frequency regulation, line mode: passes line frequency of 60Hz +/-10% Output frequency regulation, battery mode: inverter output regulated to 60Hz +/-0.5Hz Overload protection: 20A input breaker
INPUT
Maximum input: 15A, 1770 watts Recommended electrical service: 120V, 20A
BATTERY
Full load runtime: 11 minutes (2200VA) Half load runtime: 27 minutes (1100VA) Expandable battery runtime: extended runtime with optional BP24V33 external battery pack (multi-pack compatible). Capacity de-rates to 1600VA / 1280 watts with 1 external BP and 1250VA / 800 watts with 2 external BPs DC system voltage: 24 V DC Typical battery lifespan: 3-6 years, depending on usage Battery recharge rate: 2-4 hours to 90%
VOLTAGE REGULATION
Line interactive UPS offers 2 boost levels of brownout correction and a single level of overvoltage adjustment to maintain usable, computer grade output without consuming battery power. Overvoltage correction: Input voltages between 127 and 140VAC are reduced by 12% Direct pass through: Input voltages between 110 and 127VAC are passed through unchanged Brownout correction: Input voltages between 95 and 105VAC are boosted by 10% Severe brownout correction: Input voltages between 87 and 94VAC are boosted by 22%
|
|
Returns Policy
|
This product is subject to our return policy. Please see our complete return policy for details.
|
|
System Requirements
|
CD-ROM drive Available serial port
|
|
Warranty - Labor
|
2 Years
|
|
Warranty - Parts
|
2 Years
|
|
Warranty Details
|
2-year warranty, 3 year with registration. Note: registration is required for 3-year warranty. Connected Equipment Insurance (U.S., Canada & Puerto Rico) $250, 000 Ultimate Lifetime Insurance
|