- Provides 208V, 8kW 8000VA power / Surge Suppression is Standard
- 1 Outlets
- 9 minute(s) Battery Runtime at Full Load / Attributes include Double conversion online
Crowded data centers and racks filled to capacity with storage devices, monitors, servers communications devices, and other equipment are driving the need for uninterruptible power with increased power density and power efficiency. The HP 3-Phase Uninterruptible Power System gives you that. The rack-mountable Uninterruptible Power Systems provides 8,000 watts of power in a 6-U rack form factor. The UPS R8000/3 uses digital signal processing and a new On-line On Demand hybrid technology to answer the demands for increased power density and power efficiency.
On-line On Demand combines the efficiency of a line interactive UPS, up to 97%, with the stability of a double conversion on-line UPS when power fluctuates beyond acceptable limits. Hot swappable batteries and electronics modules and an automatic bypass will reduce your MTTR (mean time to repair) down time in the event service is needed.
|
Connectivity
|
|
|
Communication Interface
|
Ethernet
|
|
Communication Interface
|
Serial (RS-232)
|
|
# Ports
|
1
|
|
General
|
|
|
Attributes
|
Double conversion online
|
|
Color
|
Black
|
|
Form Factor
|
6U Rackmount
|
|
Power
|
|
|
Power Provided
|
208 V
|
|
Power Provided
|
8 kW
|
|
Power Provided
|
8000 VA
|
|
Surge Suppression
|
Standard
|
|
Battery Run Time (max)
|
9 minute(s)
|
|
Actual Weight
|
135.00 lb(s)
|
|
Compatibility Notes
|
Key Features
Unity Rated, volt amperage out equals wattage out Highest wattage per U space. Up to 12000 VA/12KW in only 6U Industry leading efficiency with On-line On Demand hybrid technology Attached line cords for easier and faster connection to your facility power Hot-swappable battery and electronics modules provide ease of maintenance and faster time to repair (MTTR) Industry leading efficiency with On-line On Demand hybrid technology Attached line cords for easier and faster connection to your facility power Extra long battery life with Enhanced Battery Management (EBM) Extended battery run time with optional Extended Runtime Modules (ERMs) Easy configuration through enhanced front panel display or HP UPS Management Module (included) Backed by a limited three-year warranty, HP's pre-failure warranty and a load protection guarantee
|
|
Contents
|
UPS, software, documentation
|
|
Physical Dimensions
|
10.3"h x 14.4"w x 26"d
|
|
Ports/Connectors
|
(1) NEMA L15-30R outlet (1) NEMA L21-30 (30A) input connector
|
|
Power Notes
|
Output
Power Output: 8kVA/8KW @ 208V 3F Delta Nominal output frequency: 50-60 Hz auto-detection (Normal mode), 50 or 60Hz (Battery mode) Output Frequency Variation: Normal mode Synchronized; Battery mode +/-0.1 when not synchronized with source Output overload: 100-110% load transfers to Bypass mode after 10 minutes; 110-125% load transfers to Bypass mode after 1 minute; 125-150% load transfers to Bypass mode after 5 seconds; >150% load transfers to Bypass mode after 300 ms Voltage wave form: Sine wave; 2% THD with typical PFC load Surge suppression: High-energy 6500 A peak Noise filtering: MOVs and line filter
Input
Voltage Range: 200-240V 3-phase Wye Nominal voltage: 208V 3-phase Wye Nominal frequency: 50/60Hz Frequency range: 45-65Hz Efficiency: 97% @ 40-100% load
Battery runtime, internal battery full load: 9 minutes (8000W) Battery runtime, internal battery half load: 23 minutes (4000W)
|
|
Returns Policy
|
This product is subject to our return policy. Please see our complete return policy for details.
|
|
Warranty - Labor
|
1 Year
|
|
Warranty - Parts
|
3 Years
|
|
Warranty Details
|
1 year onsite
|