PC Connection Clearance Center. Shop Now!

PC Connection Interactive eCatalog

Messages

          Minuteman CPE Series 2000VA 1400W 120VAC Online UPS Extended Runtime (4) 5-15R, (2) 5-15 20R

          More From: Minuteman - UPS
          Item #: 6743913
          Mfr. Part#: CPE2000
          Availability: In Stock
          Est. Ship: Ships in 24 Hours

          • Provides 2000VA, 1400watt(s) power
          • Surge Suppression is Standard
          • Connector(s): Power NEMA 5-15 (F), Power NEMA 5-20 (M), Power NEMA 5-20 (F)
          • 6 Outlets
          • 7.7 minute(s) Battery Runtime at Full Load
          • Attributes include Double conversion online

          Ordering Information

          Price:
          $679.61
           
          The MINUTEMAN CPE2000 is a 2000VA/1400W 120 VAC true on-line, double-conversion, extended runtime UPS designed for critical, power-sensitive electronic environments. Its online, double conversion technology with true sine wave output is perfect for power sensitive equipment and applications. Power factor correction (PFC) protects internal UPS components from stress and damage. You can achieve unlimited runtime with optional daisy-chained external battery packs. Remote power management through SNMP or a Web browser is available with the optional SNMP card. The UPS also provides RJ45/RJ11 network/phone protection.
          Collapse & Return to Top
          Connectivity  
          Connector Power NEMA 5-15 (F)
          Connector Power NEMA 5-20 (M)
          Connector Power NEMA 5-20 (F)
          Communication Interface Serial (RS-232)
          # Ports 6
          General  
          Form Factor Tower
          Attributes Double conversion online
          Color Black
          Power  
          Power Provided 2000 VA
          Battery Run Time (max) 7.7 minute(s)
          Power Provided 1400 watt(s)
          Surge Suppression Standard
          Actual Weight 60.00 lb(s)
          Compatibility Notes Display

          LED Indicators: Utility, Battery Low, Inverter, Bypass, Test OK, Overload Fault, Load/Battery Level, and System Fault Conditions
          Self diagnostics: on-demand push button

          Alarms

          Audible and visual: Line Failure, Battery Low, Transfer to Bypass, Overload, System Fault Conditions

          Communications Options (Available separately)

          True Relay Card: A 10-pin terminal is supported to offer the signals of Bypass, Utility Normal/Failure, Inverter On, Battery Low, Battery Bad, UPS
          Alarm, and UPS Shutdown.
          AS/400 Card: A DB9 port is supported to offer the signals of Bypass, Utility Normal/Failure, Inverter On, Battery Low, and UPS Shutdown.
          WEB/SNMP Card: Integrates multi-network communication protocols to enable comprehensive, easy-to-understand and secure remote monitoring and
          management of the UPS via the Internet.

          Operating Systems supported by UPSilon 2000 software: Microsoft Windows 95/98/NT/XP/2000/2003, Novell Netware 3.1x/4.x/5.x/6.x, Linux, and FreeBSD
          Contents UPS, communications cable, software, documentation
          Physical Dimensions 14.4"h x 5.1"w x 18.9"d
          Ports/Connectors (4) NEMA 5-15R outlets
          (2) NEMA 5-15/20R outlets
          (1) NEMA 5-20P input cord
          (2) RJ-11/RJ-45 protection jacks
          (1) DB-9 RS-232 serial communications port
          (1) Expansion slot for optional communications cards
          Power Notes Output

          Output capacity: 1400W/2000VA
          Output voltage: 120VAC
          Rated power factor: 0.7 lagging
          Load power factor range: 0.5 lagging to unity within KW rating of unit
          Wave form: sine wave, THD <3% (no load to full load)
          Voltage regulation: +/- 2%
          Transient response (ms): +/- 4% under full load, change and corrected within 60ms
          Frequency stability: +/- 0.5Hz (free running)
          Synchronization slew rate: 1Hz/sec. max synchronizing window +/-5%
          Transfer time: 0 ms
          Crest factor: 3:1

          Input

          Input voltage: 120VAC
          Frequency: 50/60Hz +/- 5% (auto sensing)
          Phase: single
          Input Power Factor Correction: >0.98 (full load)

          Battery

          User replaceable battery: Yes
          Number of internal batteries: (6)
          Replacement battery description: 12 Volt 7.2 Amp Hour
          Replacement battery part no.: 37000007
          Back-up time - full load: 7.7 minutes (1400W)
          Back-up time - half load: 19.1 minutes (700W)
          Returns Policy This product is subject to our return policy. Please see our complete return policy for details.
          UNSPSC 39121011
          Warranty - Labor 3 Years
          Warranty - Parts 3 Years
          Warranty Details $40, 000 Protected equipment insurance
          Collapse & Return to Top