PC Connection Clearance Center. Shop Now!

PC Connection eCatalog

Messages

          Tripp Lite Smart-Online 80kVA Modular UPS 3-Phase, Double Conversion Online, Hardwire Input Output

          More From: Tripp Lite
          Item #: 8682384
          Mfr. Part#: SU80KTV
          Availability: Temporarily Out-of-Stock
          Est. Ship: Call for next available delivery

          • Provides 80000VA, 64000watt(s) power
          • Surge Suppression is Standard
          • Connector(s): Hardwired
          • 1 Outlets
          • Attributes include Automatic voltage regulation (AVR), Double conversion online

          Ordering Information

          Price:
           
          Tripp Lite's SU80KTV (80kVA) SmartOnline Modular 3-Phase Intelligent, True On-Line UPS System provides 100% system availability with N+1 modular architecture and 1+1 parallel capability. In an N+1 configuration, the SU80K provides four self-contained, redundant 20kVA power modules that can be hot-swapped (with the load powered) if maintenance is required. Connect two SU80KTV models in parallel (1+1 configuration) to provide fail-safe redundancy (two 80kVA models supporting an 80kVA load) or to increase capacity (two 80kVA models supporting a 160kVA load).

          The SU80KTV provides mission-critical equipment with the highest level of power protection available. This large capacity 80,000VA/64,000W UPS continually converts incoming AC power into filtered DC power, and then resynthesizes it back into AC power with a pure sine wave. Perfectly regulated, continuous sine wave output with zero transfer time assures compatibility with all equipment types. The SU80KTV's high input power factor, advanced IGBT inverter technology and Digital Signal Processor (DSP) technology produce less than 3% input Total Harmonic Distortion (THDi). With low THDi, generators run cooler and last longer, allowing managers to save installation costs by installing a generator with a capacity equal to the equipment load (1:1 ratio). Extremely efficient operation (up to 96%) saves money by lowering electricity consumption. Hardwire input and output connections support a variety of permanent or PDU-style power connections. The SU80KTV features 277/480VAC, 3-phase, 4-wire (plus ground), wye input and output. It also features a wide input voltage correction range: 218-348/378-603VAC. Frequency is 50 or 60 Hz (auto-selectable). The SU80KTV features a single small-footprint tower power module.

          Battery runtime can be extended with optional stand-alone hardwired external battery modules (Models BP480V26B and BP480V40C with matching battery cabinets, available separately). A manual bypass breaker and an automatic bypass function ensure 100% availability of connected equipment by safely passing through AC power if the UPS requires maintenance. A built-in RS-232 communication port works with the included PowerAlert Software to provide shutdown commands and reporting on a single server. An accessory slot accepts an internal SNMP card (Model SNMPWEBCARD, available separately) for remote shutdowns, reboots and more. A front panel combination LCD/LED display alerts you to a variety of UPS operational modes and conditions. The LCD display includes a real-time event log screen with up to 500 events listed.

          A 1-year limited warranty is included and a start-up service program (available separately) is recommended to enhance the reliability of the installation.
          Collapse & Return to Top
          Actual Weight 1286.00 lb(s)
          Compatibility Notes LEDS ALARMS & SWITCHES

          Front panel LEDs: SELECTABLE LCD DISPLAY: displays Real-Time Event Log with up to 500 events listed. Also indicates a wide range of UPS operational and fault/warning conditions including operational mode, alarm/shutdown conditions, input/output voltage/frequency, battery voltage, load percentage and more. 4 LED DISPLAY: normal AC input, on battery power, bypass input and fault condition
          Alarms: Alarms signal a variety of operational conditions: low battery, overload, shutdown, bypass and more
          Switches: ON button turns UPS's inverter ON. OFF button turns UPS's inverter OFF. LCD Display Control Buttons browse through and select items displayed on LCD screen. Emergency Power Off button turns UPS output OFF and disables Bypass output. Manual Bypass breaker bypasses the UPS's inverter during maintenance

          SURGE / NOISE SUPPRESSION

          AC surge suppression: 4675 joules
          AC suppression response time: Instantaneous
          EMI / RFI AC noise suppression: Yes
          Connectivity
          # Ports 1
          Communication Interface Serial (RS-232)
          Connector Hardwired
          Contents UPS, software with cabling, parallel cable for 1+1 operation, documentation
          General
          Attributes Automatic voltage regulation (AVR), Double conversion online
          Color Black
          Form Factor Tower
          Physical Dimensions 66.9"h x 20.5"w x 33.7"d
          Ports/Connectors Outlet quantity/type: hardwire
          Input connection type: hardwire
          Power
          Power Provided 64000 watt(s), 80000 VA
          Surge Suppression Standard
          Power Notes Voltage compatibility: 277/480VAC, 3-phase, 4-wire (plus ground), wye
          Frequency compatibility: 50/60 Hz (auto-selectable)

          OUTPUT

          Output capacity: 48kW/60kVA
          Output nominal voltage: 277/480VAC, 3-phase, 4-wire (plus ground), wye
          Output voltage regulation: Maintains pure sine wave output at all times, regulated within 1% of nominal output voltage, less than 3% total harmonic distortion (using IGBT Inverter)
          Output frequency regulation: Regulates line frequency at 50 or 60Hz, +/- 0.5Hz

          INPUT

          Maximum input current: 73A (per phase, on-line)
          Recommended electrical service: 277/480VAC (3-Phase, 4 Wire, wye)

          BATTERY

          Expandable battery runtime: Requires stand-alone external battery modules (Models BP480V26B and BP480V40C with matching cabinets), available separately
          DC system voltage: 480VDC
          Typical battery lifespan: 3-6 years, depending on usage
          Battery recharge rate: 2-4 hours to 90%

          VOLTAGE REGULATION

          Voltage regulation description: On-line, double-conversion process enables UPS to maintain output voltage within +/-1% of nominal voltage at all times
          Overvoltage correction: Maintains continuous operation without using battery power during overvoltages to 348/603VAC (3-Phase, 4-Wire, wye)
          Brownout correction: Maintains continuous operation without using battery power during brownout / undervoltage conditions to 218/378VAC (3-Phase, 4-Wire, wye)
          Returns Policy This product is subject to our return policy. Please see our complete return policy for details.
          UNSPSC 39121011
          Warranty - Labor 1 Year
          Warranty - Parts 1 Year